Skip to main content

Quick Start

Hardware version

CANBench Duo v1.2 — Schematic-stage refresh of the V1.1 fabricated prototype. V1.2 is electrically identical to V1.1 and carries the InvenTree-canonical component metadata; no V1.2 boards exist yet — testing and bring-up reference the V1.1 hardware.

Other versions: v1.1 — fabricated prototype (current)

Six-step bench setup for the CANBench Duo. Assumes the unit is sitting flat on the test bench with the top extrusion (SMAs + M12 + LED) facing up.

  1. Connect bench supply to the front-faceplate banana pair (RED to SRC+, BLACK to SRC−). The Red banana lights GREEN if polarity is correct, RED if reversed, BLUE if F1 has blown (a brief Blue flash at supply turn-on is benign — Q2 settling — and resolves to GREEN within a few ms). See Status LED for the full state encoding.
  2. Connect DUT to the back-faceplate banana pair (RED to DUT+, BLACK to DUT−), OR via the M12 N2K connector (J10) for combined supply + CAN bus.
  3. Terminate unused SMA ports with 50 Ω. This is mandatory — unterminated ports produce false readings.
  4. Connect the spectrum analyser to the SMA port of interest via short, good-quality coaxial cable. See Spectrum-Analyser Setup for recommended configuration.
  5. Power on the bench supply. Verify the Green LED. Confirm the DUT operates normally with supply current within the 4 A continuous envelope.
  6. Sweep per the Measurement Procedure.

For deeper context on what each step protects against, see Common Pitfalls. For the LISN+/LISN− symmetry comparison and the CM/DM separation workflow, see Interpreting Results.